Standardy kołnierzy przyłączeniowych

Connection flange standards

In the sewage system we use two main connecting standards:

  • EN 1092-1 - for steel collars
  • EN 1092-2 - for cast iron collars

The difference between them in the installation is small and does not matter when connecting one with another. It is important to maintain the compatibility of PN nominal pressure for collars because they determine the amount and spacing of holes for the screws on the diameter.

The table below presents typical connections and their diameters:

Pressure

PN6

PN10

PN16

Diameter

Bolts

Bolts

Bolts

Dn Quantity / thread / spacing Quantity / thread / spacing Quantity / thread / spacing

DN15

4

M10

55

4

M12

65

4

M12

65

DN20

4

M10

65

4

M12

75

4

M12

75

DN25

4

M10

75

4

M12

85

4

M12

85

DN32

4

M12

90

4

M16

100

4

M16

100

DN40

4

M12

100

4

M16

110

4

M16

110

DN50

4

M12

110

4

M16

125

4

M16

125

DN65

4

M12

130

4/8

M16

145

4/8

M16

145

DN80

4

M16

150

8

M16

160

8

M16

160

DN100

4

M16

170

8

M16

180

8

M16

180

DN125

8

M16

200

8

M16

210

8

M16

210

DN150

8

M16

225

8

M20

240

8

M20

240

DN200

8

M16

280

8

M20

295

8

M20

295

DN250

12

M16

335

12

M20

350

12

M24

355

DN300

12

M20

395

12

M20

400

12

M24

410